Goodman Heat Pump Error Codes: What Each Code Means and What to Do

When a Goodman heat pump with a diagnostic display stops on a fault, the control board shows a two-character code instead of its normal status. This guide lists the Goodman heat pump error codes, what each one means, what usually causes it, which ones you can check yourself and what the fix tends to cost.

The definitions come from Goodman’s own documents: the installation and service reference for its ComfortBridge heat pumps and condensing units (IOG-4009O, June 2023) and the service instructions for its ComfortNet heat pumps and air handlers (RS6200007). Both are written for technicians, so this guide puts them in plain English.

Goodman heat pump error codes: outdoor heat pump unit in the rain
Photo: Sam Jotham Sutharson / Unsplash

Does your Goodman show codes at all?

Not every Goodman heat pump has a code display. The codes in this guide come from the control board on Goodman’s communicating two-stage models: the GSZC7 and the earlier GSZC16, GSZC18 and DSZC series (the ComfortBridge and ComfortNet ranges). On those units, three small 7-segment digits on the control board inside the outdoor unit show the code.

If your outdoor unit has no display, it uses a simpler defrost control and the table below doesn’t apply. In that case the symptom is the clue: no heat, cold air, constant icing or a unit that won’t start. Our guides to a heat pump blowing cold air and a frozen heat pump cover those.

The display sits behind the outdoor unit’s service panel, next to live high-voltage wiring. Reading it is a job for your technician. What you can do is tell them what the system was doing when it stopped, and what the indoor unit or thermostat shows.

Codes that aren’t faults

On Goodman’s communicating air handlers, the indoor display also shows status codes during normal operation:

  • dF means the system is defrosting. The outdoor coil is being warmed to melt frost, and Goodman ends a defrost when the coil reaches about 75°F or after 10 minutes, whichever comes first.
  • H1 and H2 mean the electric backup heat is running on low or high stage. On non-communicating setups, H1 can also appear during defrost.
  • h1 and h2 mean emergency heat, low or high.
  • FC, FH and F mean the fan is running for cooling, for heating, or on its own.

Goodman outdoor unit error codes: full list

CodeWhat it meansUsual causes
01Low side fault (low-pressure trip)Low refrigerant charge, a restriction in the liquid line, the indoor blower not running, or the thermostat set extremely low
L1Low-pressure lockout: three 01 tripsSame as 01. The unit stays off until power is cycled
02High side fault (high-pressure trip)Dirty or blocked outdoor coil, outdoor fan not running, a fan wiring fault or a failed fan capacitor
L2High-pressure lockout: three 02 tripsSame as 02. The unit stays off until power is cycled
03Short cyclingThe thermostat calling on and off intermittently, or a faulty compressor relay. The board enforces a 3-minute minimum run time
04Locked rotorSeized compressor bearings, a failed run capacitor or its wiring, or low line voltage
05Open circuitPower disconnected, a tripped breaker or blown fuse, a failed compressor protector or a compressor wiring fault
06Open start circuitOpen start winding in the compressor, a capacitor fault or a wiring fault
09Low control voltage (below 18 VAC)Overloaded transformer, low line voltage or a fuse problem
P0Compressor protector openNo current through the compressor windings: an open run winding, a wiring fault or a capacitor fault
H8High line voltage (above 255 VAC)The power supply to the house or unit is too high. Clears once voltage drops back below 255 VAC
L8Low or no line voltage (below 185 VAC)Tripped breaker, blown fuse or low supply voltage
A2Outdoor air temperature sensor faultSensor shorted, open, unplugged or reading out of range. The heat pump won’t heat
A3Outdoor coil temperature sensor faultSame as A2, for the coil sensor. The unit won’t run
E5Control fuse openA short in the low-voltage (thermostat) wiring blew the board’s 3-amp fuse
EEControl board faultCompressor relay contacts welded shut. The board needs replacing
b0Indoor blower not running when it should beBlower motor fault, indoor wiring, or lost communication between the indoor and outdoor units
b9Airflow lower than the system asked forClogged filter, restrictive or undersized ductwork, an indoor blower fault, or indoor and outdoor units that don’t match
d0System data not yet on the networkThe communicating system hasn’t shared its setup data. Clears once the data loads
d1Invalid data on the networkWrong or invalid setup data for the equipment
d2System mismatchThe outdoor unit needs more airflow than the indoor unit can supply, or the shared data is incompatible
d3Configuration mismatchSetup data doesn’t match the installed hardware
d4Invalid memory card dataThe control rejected the data on the installer’s memory card

The d-codes almost always show up right after installation or a part replacement. They are a setup problem for the installer, not a failure of the equipment.

Goodman indoor unit (air handler) codes

Goodman’s communicating air handlers have their own display. When one of these codes appears, a communicating thermostat usually shows “Check Air Handler” or a call-for-service icon.

CodeWhat it meansUsual causes
EFAuxiliary switch openHigh water level in the coil’s drain pan, usually a clogged condensate drain
EcHeat kit mismatchThe electric heat kit settings don’t match the system’s setup data
E5Fuse openA short in the low-voltage wiring
EEInternal fault or no powerPower off, a tripped breaker or blown fuse, or a loose 24-volt connection
b0Blower motor not runningLoose motor wiring or a failed motor
b1Blower motor not communicatingLoose control wiring, a failed motor or a failed control
b2Motor size mismatchWrong motor or wrong setup data
b3Motor at its power, temperature or speed limitBlocked filter, restrictive ductwork or high ambient temperature
b4Motor current tripAbnormal load or a sudden airflow blockage
b5Blower rotor lockedSomething jammed in the blower housing, or seized bearings
b6Motor voltage or temperature faultIncorrect line voltage or high ambient temperature
b7Motor didn’t receive its settingsA control error or repeated failed motor starts
b9Low indoor airflowBlocked filter or restrictive ductwork
d0, d1, d4Setup data missing or invalidSame meaning as on the outdoor unit

A fault and a lockout aren’t the same

The most useful thing to understand about Goodman’s codes is the difference between a fault and a lockout.

A pressure fault (01 or 02) means a safety switch opened once. The board stops the compressor, waits and tries again. If the next cycles run normally, the code clears on its own: after three normal cycles for 01 and four for 02. That’s why the display can be blank by the time a technician arrives.

A lockout (L1 or L2) means the same switch opened three times. The board now stays off until someone cycles the 24-volt power, usually by turning the system off at the thermostat or switching the breaker off and on. Goodman treats a locked rotor (04) the same way.

Carrier works on similar logic with its fault code 84, a four-hour high-pressure lockout.

How to see past faults

The board keeps the six most recent faults, newest first. With the system idle, a technician presses the RECALL button for 2 to 5 seconds to scroll through them. Holding it longer than 5 seconds clears the history, which Goodman recommends after a repair.

Ask for that history to be read before any part is replaced, and to be cleared after the repair. A pattern, such as 02 every afternoon in summer or 01 every cold morning, says more than a single code.

What you can safely check yourself

  • The air filter. Goodman lists a clogged filter as a cause of b9 and b3, and poor indoor airflow can also contribute to 01. Replace it if you can’t see light through it.
  • Registers and returns. Make sure supply vents are open and nothing blocks the return grille.
  • The outdoor unit. Clear leaves, snow, ice and anything stacked against it. A blocked outdoor coil is one of the causes Goodman lists for 02 and L2. With the power off, you can rinse the coil gently with a garden hose, never a pressure washer.
  • Breakers. A tripped breaker or pulled disconnect gives 05 or L8. Reset it once. If it trips again, stop and call a technician.
  • The condensate drain. EF on the air handler usually means the drain is clogged and the pan is full.
  • The thermostat. Check the mode, the setpoint and the batteries. Intermittent thermostat calls cause 03.

Leave pressure switches, capacitors, refrigerant and the control board to a licensed technician. Jumping a safety switch to get the unit running can destroy the compressor.

How to reset a Goodman heat pump

Turn the system off at the thermostat, switch off the outdoor unit’s breaker for a minute, then restore power and turn the system back on. That cycles the 24-volt control power, which is what Goodman’s manual says clears lockouts such as L1, L2 and 04.

Reset once. If the same code comes back, the cause is still there. Repeated resets against a high-pressure or locked-rotor fault strain the compressor, the most expensive part in the system.

What Goodman repairs usually cost

RepairLikely codesTypical cost
New filter, clearing the outdoor unitb9, b3, 02$0 if you do it
Diagnostic visitAny$75–$250
Run capacitor02, 04, 06, P0$100–$400
Temperature sensor or defrost controlA2, A3, defrost problemsLess for a sensor; $200–$500 for a defrost board
Control boardEE, E5 (if the fuse keeps blowing)$150–$700
Outdoor fan or indoor blower motor02, L2, b0, b5$200–$1,000 (up to $1,500 for a variable-speed blower)
Reversing valveHeating or cooling problems, no code$350–$1,200
Refrigerant leak repair01, L1$200–$1,500, plus the refrigerant
Compressor04, 06, P0 (once wiring and capacitor are ruled out)$800–$4,000

Ranges come from PickHVAC (May 2026), Fixr (January 2026) and HVAC.com. If the part is under warranty, you mostly pay for labor. To compare the price of a whole new system instead, see our heat pump installation cost by state.

Is it covered by the warranty?

Goodman’s May 2025 warranty chart lists a 10-year parts limited warranty and a 10-year unit replacement limited warranty on models including the GSZC7 and GSZV9, but only if the system is registered online within 60 days of installation. Registration isn’t required in California, Florida or Québec. Check your registration before you pay for a part, and ask the technician to write the code and the fault history on the invoice.

Frequently asked questions

Where is the error code on a Goodman heat pump?

On ComfortBridge and ComfortNet models, it shows on a small three-digit display on the control board inside the outdoor unit’s service panel. Communicating air handlers have their own display, and a communicating thermostat may show “Check Air Handler” or a service icon.

What does L2 mean on a Goodman heat pump?

L2 is a high-pressure lockout: the high-pressure switch opened three times. Goodman lists a blocked outdoor coil, an outdoor fan that isn’t running, fan wiring or a failed fan capacitor as the usual causes. It stays locked out until the control power is cycled.

What does b9 mean on a Goodman?

The system is getting less airflow than it asked for. Start with the filter and make sure the vents and return grille aren’t blocked. If it continues, the blower or the ductwork needs checking.

Is dF an error?

No. dF on a Goodman communicating air handler means the heat pump is defrosting. A Goodman defrost ends when the outdoor coil warms to about 75°F or after 10 minutes at most.

How do I clear a Goodman error code?

Pressure faults such as 01 and 02 clear on their own after a few normal cycles. Lockouts such as L1, L2 and 04 clear when you cycle power at the thermostat or breaker. The board still keeps the last six faults in its history.

Sources